Notes:
1786 SQ FT, CIFO / SPEC SPACE #420
3/7/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. ALL CEILING AND WALL FINISHES SHALL COMPLY WITH 2003 IBC SECTION 803 FOR FLAME AND SMOKE SPREAD INDEX/RATING.
2. ANY WOODS SHALL BE FIRE RETARDANT WOOD ON A TYPE II-B CONSTRUCTION AS REQUIRED BY CITY OF FRISCO.
3. SAFETY GLAZING AS REQUIRED IN 2003 IBC 2406.
4. PENETRATION ON A 1-HOUR FIRE RATED DEMISING WALL SHALL NOT BE REDUCED, FIRESTOP SYSTEM SHALL BE INSTALLED AND MATERIALS SHALL BE TESTED IN AN APPROVED ASSEMBLY.
5. COMBINATION FIRE/SMOKE DAMPERS REQUIRED IN DUCTS PENETRATION ON A 1-HOUR FIRE RATED WALL CONSTRUCTION
6. SUBJECT TO FIELD REVIEW AND INSPECTION.