Notes:
1311 SQ FT, CIFO / JONES NEW YORK APPAREL
2/28/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. NEW WALL AND DOOR B/6/4 FOR THE ADJACENT TENANT WILL CREATE A DEAD END SITUATION, CITY OF FRISCO AMENDMENTS SPECIFY THAT DEAD END CORRIDOR SHALL BE 20 FEET MAXIMUM. THEREFORE MOVE THE WALL AND DOOR B/6/4 FOUR (4) FEET TOWARDS NORTH TO ELIMINATE DEAD END SITUATION.
2. ALL CEILING AND WALL FINISHES SHALL COMPLY WITH 2003 IBC SECTION 803.
3. ANY WOODS SHALL BE FIRE RETARDANT WOOD ON A TYPE II-B CONSTRUCTION AS REQUIRED BY CITY OF FRISCO.
4. SAFETY GLAZING AS REQUIRED IN 2003 IBC 2406.
5. PENETRATION ON A 1-HOUR FIRE RATED DEMISING WALL SHALL NOT BE REDUCED, FIRESTOP SYSTEM SHALL BE INSTALLED AND MATERIALS SHALL BE TESTED IN AN APPROVED ASSEMBLY.
6. COMBINATION FIRE/SMOKE DAMPERS REQUIRED IN DUCTS PENETRATION ON A 1-HOUR FIRE RATED WALL CONSTRUCTION
7. SUBJECT TO FIELD REVIEW AND INSPECTION.