Notes:
285 SQ FT, CALT / STEWART CREEK CORRIDOR
3/20/2007 12:00:00 AM
1. THE DOOR AND WALL BETWEEN CORRIDOR AND THE MIDDLE STAIR AREA IS NOT INCOMPLIANCE WITH THE APPROVED SHELL BUILDING PLAN (SEE MARKED DRAWINGS).
2. ALL CEILING AND WALL FINISHES SHALL COMPLY WITH 2003 IBC SECTION 803 FOR FLAME AND SMOKE SPREAD INDEX/RATING.
3. FIRE RATED CORRIDOR WALL SHALL BE TYPE II-B NONCOMBUSTIBLE CONSTRUCTION.
4. PENETRATION ON A 1-HOUR FIRE RATED DEMISING WALL SHALL NOT BE REDUCED, FIRESTOP SYSTEM SHALL BE INSTALLED AND MATERIALS SHALL BE TESTED IN AN APPROVED ASSEMBLY.
5. COMBINATION FIRE/SMOKE DAMPERS REQUIRED IN DUCTS PENETRATION ON A 1-HOUR FIRE RATED WALL CONSTRUCTION
6. DOOR THAT OPENS TO THE CORRIDOR SHALL BE PROTECTED BY 20 MINUTES FIRE RATED ASSEMBLY.
7. SUBJECT TO FIELD REVIEW AND INSPECTION.