Notes:
597 AC 1867 SQ FT, SADD / 3 CAR GARAGE, PATIO & RENOVATIONS
2/19/2007 12:00:00 AM
02. COMPLIANCE WITH THE 2003 CODES, AMENDMENTS, ORDINANCES & SUBDIVISION REQUIREMENTS.
03. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
10. BEAMS=10"W X 28"D.
25. TEMPERED GLASS REQ'D AT WINDOWS WITHIN 2' OF DOOR OPENINGS.
29. TEMPERED GLASS AT FLOAT GLASS WINDOWS GREATER THAN 9 SQ FT, LESS THAN 18" OFF FINISH FLOOR, WITHIN 3'-0" OF A WALKING SURFACE.
33. MEDIA ROOM WITH CLOTHING STORAGE MUST HAVE A CODE COMPLIANT EGRESS WINDOW.
34. SIDING & TRIM MUST BE CEMENT FIBER OR ENGINEERED TREATED WOOD PRODUCT.
35. 2 X 6 PLUMBING (VENT STACK/WASTE) WALLS REQ'D AT ALL FIXTURES.
44. CO DETECTORS REQ'D ON ELECT LEGEND & ELECT PLAN 1/1000 SQ FT & 1 PER FLOOR MIN PLUS (1) ADD'L AT GARAGE ENTRY IN AC AREA.
50. CSST GAS PIPING ALLOWED - SEE INFO SKETCH IN LOBBY AND (OR) ORDINANCE(S) 03-07-58 & 03-07-59.
54. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
55. FUEL BURNING HOT WATER HEATER INSTALLATION MUST BE CODE COMPLIANT.
60. BUILDER CAUTION: CONSTRUCTION NOT CONFORMING TO THE ABOVE PERMIT REQUIRMENTS COULD RESULT IN C.O. DELAY OR POSSIBLE DENIAL.
a/c and garage 5379 sq. ft. this is with additions-- no fire sprinkler req'd.
5/8" type X gyp. bd. req'd. in garage -- 1 hr. fire separation from conditioned space.--------------------sag resistant ceiling rated gyp. board req'd. in living.
slab---w/ 2 #5's top & bottom of beam---------also 4's @ 18" o.c.e.w.
2x6 vent walls req'd. @ bath.
install combo smoke/carbon monoxide detector 10' from garage service door.
21" clear space from obstructions in front of water closet.
R1001.6---chimney shall extend at least 2' higher than any portion of a bldg. within 10' (roof) but shall not be less than 3' above the highest point where chimney passes roof.