PLAN REVIEW COMMENTS;
1. IN DETERMINING THE OCCUPANT LOAD THE LARGEST NUMBER COMPUTED IN ACCORDANCE WITH SECTION 1004.1.1 THROUGH 1004.1.3 SHALL BE USED AND ON THIS CASE THE NUMBER COMPUTED BASED ON OCCUPANT PER UNIT AREA AS PRESCRIBED IN TABLE 1004.1.2 WILL PRODUCE LARGEST NUMBER OF PEOPLE. CUSTOMER AREA = 838 SQFT / 15 (FACTOR) = 56 PEOPLE AND KITCHEN AREA = 772 / 200 = 4 PEOPLE, TOTAL OF 49 PEOPLE.
2. SPACE THAT HAS 50 OR MORE PEOPLE REQUIRES AT LEAST TWO EXITS AND THAT EGRESS SHALL NOT PASS THROUGH AN INTERVENING ROOM SUCH AS KITCHEN, STORAGE AND OTHER SIMILAR SPACES THEREFORE SUBMIT REVISED FLOOR PLAN THAT SHOWS TWO MEANS OF EGRESS THAT COMPLIES (SEE IBC 1014.1 AND 1013.2).
3. MECHANICAL VENTILATION SHALL BE PROVIDED BY A METHOD OF SUPPLY AIR AND RETURN AIR , THE MECHANICAL PLAN DOES NOT SHOW RETURN AIR TAKEN FROM THE KITCHEN AREA THAT WILL CREATE EITHER NEGATIVE OR POSITIVE PRESSURE ON THE SPACE WHICH THE IMC 403.1 DOES NOT ALLOW. SUBMIT REVISED PLAN.
4. PENETRATIONS ON THE FIRE RATED WALL CONSTRUCTION SHALL BE INSTALLED AS TESTED IN AN APPROVED FIRE-RESISTANCE RATED ASSEMBLY WITH APPROVED FIRESTOP SYSTEM (IBC 712.3).
(2/16/2007 15:54 JS) A1.01 - PROVIDE 1DEDICATED FOOD PREPARATION SINK IN KITCHEN AREA OR PROVIDE INSERT FOR 3-COMPARTMENT SINK THAT PROTECTS FOOD AND DOES NOT ALLOW FOOD TO TOUCH SINK. BEVERAGE COOLER SHALL CONTAIN ONLY PREPACKAGED BOTTLED DRINKS; PROVIDE SMOKING SIGNAGE AT ENTRANCES "SMOKING IS PROHIBITED OFFENSE PUNISHABLE BY FINE NOT TO EXCEED $2,000 (TWO-THOUSAND DOLLARS); RESTROOM DOORS SHALL BE SELF-CLOSING; PROVIDE APPROVED FLOORING IN REFRIGERATED WALK IN. A2.01 - GREASE INTERCEPTOR SHALL BE SIZED ACCORDING TO THE FORMULA AS CITED ON THE PLAN. 100 GALLON IS UNAPPROVED. WATER HEATER MINIMUM SIZE OF 56 GPH AND 12.0 KW IS REQUIRED. SEE SIZING SHEET ATTACHED TO PLAN.