Notes:
3200 SQ FT, CNEW / LEBANON CHURCH
12/21/2006 12:00:00 AM
PLAN REVIEW COMMENTS;
1. DOORS 3 AND 4 SHALL HAVE 36" MINIMUM WIDTH TO COMPLY WITH ADA REQUIREMENTS.
2. SAFETY GLAZING REQUIRED ON WINDOW 5 THAT IS WITHIN 24" FROM THE EDGE OF THE DOORS 2, 6 AND 8.
3. TO COMPLY WITH ADA REQUIREMENT THE PLATFORM SHALL HAVE AT LEAST ONE HANDRAIL NEAR WINDOW 3.
4. PROVIDE HI/LO DRINKING FOUNTAIN.
5. MOPSINK REQUIRED.
6. MECHANICAL EXHAUST FAN SHALL BE PROVIDED IN THE RESTROOMS, ALSO MAKE-UP AIR SHALL BE PROVIDED.
7. WINDOWS BEING REPLACED SHALL BE INCOMPLIANCE WITH THE PRESCRIPTIVE APPROACH OF THE ENERGY CODE; U-VALUE=0.60 MAX., SHGC VALUE=0.40 MAX.
8. HANDRAILS IN THE ACCESSIBLE RAMP AND STAIR SHALL HAVE A CURB OR BARRIER THAT PREVENTS THE PASSAGE OF A 4 INCH DIAMETER SPHERE BELOW A HEIGHT OF 4 INCHES.
9. RESTROOMS FLOOR AND WALL FINISH SHALL HAVE A HARD, SMOOTH AND NON-ABSORBENT SURFACE.
10. MECHANICAL AND PLUMBING PLANS WERE NOT SUBMITTED, NO SITE PLAN AND NO FOUNDATION PLAN.
11. SUBJECT TO FIELD REVIEW AND INSPECTION.