Notes:
10640 SQ FT, CIFO / KIMLEY HORN
12/22/2006 12:00:00 AM
1. SPACE ON THE SOUTH SIDE OF THE BUILDING THAT HAS AN OCCUPANCT LOAD OF MORE THAN 50 REQUIRES AT LEAST TWO EXITS, THEREFORE DOORS D AND A SHALL SWING TOWARDS THE PATH OF EXIT TRAVEL (2003 IBC 1008.1.2).
2. DOOR ASSEMBLIES IN CORRIDOR WALLS SHALL BE PROTECTED AS FOLLOWS; DOORS WITH GLAZING SHALL HAVE 20 MINUTES FIRE PROTECTION RATING (2003 IBC 715.3.3), SIDELITES/FIXED WINDOW OR GLAZING SHALL HAVE 45 MINUTES FIRE PROTECTION RATING (2003 IBC 715.3.3 AND 715.4), FRAME WHICH THE CITY OF FRISCO CONSIDER AS PART OF THE WALL SHALL HAVE 1-HOUR FIRE PROTECTION RATING.
3. SAFETY GLAZING REQUIRED FOR DOOR A WITH SIDELITE AND SIDELITE NOTE 76 (2003 IBC 2406.3).
4. MEMBRANE PENETRATIONS SHALL BE PROTECTED BY AN APPROVED PENETRATION FIRESTOP SYSTEM (2003 IBC 712.3.2).
5. COMBINATION FIRE/SMOKE DAMPERS REQUIRED ON DUCTS AND AIR TRANSFER OPENINGS THAT PENETRATES A FIRE RATED WALL ASSEMBLIES (2003 IBC 716).
6. DUCT PENETRATION THROUGH AN EXIT STAIRWAYS ENCLOSURE IS PROHIBITED UNLESS NECESSARY FOR INDEPENDENT PRESSURIZATION, THEREFORE REVISED THE PLAN OR RELOCATE THE 84X18 THAT PENETRATES INTO THE EXIT STAIRWAY ENCLOSURE (2003 IBC 1019.1.2).
7. ANY WOODS USED IN A TYPE II-B CONSTRUCTION SHALL BE FIRE RETARDANT TREATED WOOD.
8. FLAME SPREAD AND SMOKE INDEX REQUIREMENTS SHALL COMPLY WITH 2003 IBC TABLE 803.5.
9. SUBJECT TO FIELD REVIEW AND INSPECTION.