Notes:
3191 SQ FT, CIFO / FRISCO SQUARE DEVELOPMENT CO
1/3/2007 12:00:00 AM
1. THE BUILDING HAS A TYPE I-B CONSTRUCTION CLASSIFICATION THEREFORE THE STRUCTURAL BUILDING ELEMENTS SUCH AS COLUMNS, GIRDERS AND TRUSSES SHALL BE PROTECTED BY AT LEAST 2-HOUR FIRE RESISTIVE CONSTRUCTION. DETAIL 13/A7.01 FOR TYPICAL COLUMN ENCLOSURE MUST HAVE 2-HOUR FIRE RESISTIVE PROTECTION NOT 1-HOUR.
2. THE SPACE REQUIRES 2-EXITS AND HAS AN OCCUPANT LOAD OF MORE THAN 50 PERSONS THEREFORE THE SECOND MEANS OF EGRESS GOING INTO THE EXIT ACCESS CORRIDOR SHALL SWING TOWARDS THE PATH OF EXIT TRAVEL, IN ORDER NOT TO BLOCK THE CORRIDOR IT SHOULD BE RECESSED FROM THE CORRIDOR AND THE DOOR MUST STILL HAVE THE 18" MINIMUM CLEARANCE BEYOND LATCH PARALLEL TO DOOR.
3. 1-HOUR FIRE RATED DEMISING WALL BETWEEN TENANTS REQUIRED.
4. RESTROOMS WALL AND FLOOR SHALL HAVE A HARD, SMOOTH, AND NON-ABSORBENT SURFACE. RESTROOMS MUST ALSO COMPLY WITH TAS/ADA REQUIREMENTS.
5. SUBJECT TO FIELD INSPECTION.
***CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.***