PLAN REVIEW COMMENTS;
1. OFFICE 104, 106, 107, 108 FLOOR PLAN LAY-OUT SHALL BE REVISED AS PER ADA REQUIREMENTS, REDMARK COMMENTS SHALL BE COMPLIED OR SUBMIT REVISED DRAWING SHOWING COMPLIANCE WITH MANUEVERING CLEARANCES AT DOORS. WHERE BOTH CLOSER AND LATCH ARE PROVIDED A FRONT APPROACH/PUSH SIDE SHALL HAVE 12" MINIMUM CLEARANCE PARALLEL TO DOOR.
2. DOORS OPENINGS INTO A 1-HOUR FIRE RATED CORRIDOR SHALL BE 20 MINUTES FIRE RATED ASSEMBLY.
3. EXISITING DEMISING WALL SHALL BE 1-HOUR FIRE RATED CONSTRUCTION AND LIKEWISE CORRIDOR SHALL BE 1-HOUR.
4. PENETRATIONS ON 1-HOUR FIRE RATED WALL SHALL BE OF FIRE RESISTIVE MATERIALS AND WITH FIRE STOP SYSTEM.
5. WALL AND CEILING FINISH SHALL HAVE A MINIMUM FLAME SPREAD RATING OF 76-200, SMOKED INDEX 0-450.
6. SUBJECT TO FIELD INSPECTION.