PLAN REVIEW COMMENTS;
1. PROVIDE WALL AND DOOR AT CORRIDOR 303 IN ORDER NOT TO CREATE A DEAD END SITUATION (SEE NOTES ON PLANS).
2. ANY WOODS USED IN THIS PROJECT SHALL BE FIRE RETARDANT TREATED WOOD.
3. CONNECTION BETWEEN DEMISING WALL AND MULLION SHALL FIRE/SMOKE PROOF OR FIRE SAFING SHALL BE PROVIDED (DETAIL SHALL BE SUBMITTED.
4. ANY PENETRATION ON 1-HOUR DEMISING WALL SHALL NOT REDUCED ITS FIRE RESISTANCE.
5. SIDELITE NEAR DOOR M/1/5 SHALL BE TEMPERED WITH 45 MINUTES FIRE PROTECTION RATING.