Notes:
630000 SQ FT, CADD / FIRST UNITED METHODIST CHURCH PARKING
11/14/2006 12:00:00 AM
PALN REVIEW COMMENTS;
1. AS PER 2003 IBC TABLE 1106.1 THE REQUIRED NUMBER OF ACCESSIBLE PARKING SPACES SHALL BE 7 WITH 2 ACCESSIBLE VAN PARKING INCLUDED (2003 IBC 1106.5).
2. SUBJECT TO FIELD INSPCETION.
(11/17/2006 09:16 JM)
see attached Lighting and Glare Ordinance
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2003 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.