Notes:
4689 SQ FT, CIFO / SPEC SPACE #110
8/23/2006 12:00:00 AM
Plan review comments;
1. The space requires to have 2 exits for two reasons, first the occupant load is more than 50 (IBC 1014.1 and table 1014.1) and second the common path of egress travel is more than 100 feet from the most remote portion of the space (IBC 1013.3), therefore door C shall be recessed back into the space and needs to swing towards the path of egress travel furthermore wall and door frame shall have 1-hour protection and 20 minutes for door.
2. Side lite shall have safety glazing.
3. Any penetrations to a fire resistive wall construction shall not reduced its ratings.
4. Provide additional exit ligth/sign above door C.
(10/2/2006 15:39 SEL) PLUMBING - PREMIER SERVICES & ELECTRICAL - WALKER ENG HAVE BOTH EXPIRED. CONTRACTOR IS TO LET THEM KNOW THEY WILL NEED TO REGISTER IN ORDER TO HAVE INSPECTIONS.