26000 SQ FT, CIFO / IGNITE TECHNOLOGIES
8/15/2006 12:00:00 AM
Plan review comments and requirements;
1. The door or opening in between reception 300 and elevator lobby is not allowed, access to space which is a potential area that could build a rapid fire and smoke is prohibited (see IBC 1013.2). The intent of the code is separate the elevator from the rest of the space inside the building and elevator lobby is not intented to be used as a means of egress. Submit revised plan.
2. Interior finishes shall comply with IBC Table 803.5
3. Safety glazing required as per IBC 2406.
4. Subject to field inspection.