Notes:
450 SQ FT, CNEW / CROWN RIDGE AMENITY CENTER
8/21/2006 12:00:00 AM
Plan review comments.
1. Any wood sleepers and sills on a concrete or masonry slab that is direct contact with earth shall be of naturally durable or preservative-treated wood(IBC 2304.11.2.3).
2. Main door shall swing in the direction of egress travel where serving an occupant load of 50 or more persons (IBC 1008.1.2)
3. Safety glazing required on windows that is within 24" of the edge of the doors(IBC 2406).
4. Subject to field inspection.
(6/26/2006 16:25 PB)
Comments and requirements:
1. In this particular plan the code requires two (2) exits a minimum of 48 inches on each, the exits shall be placed at least 1/2 of the total diagonal distance of space underconsideration.
2. The code also requires that the new gate/exit shall have landing or walkway that connect to the new walkway and ADA/TAS compliant.
3. Due to the occupant load of 432 the code requires 2 water closet, 2 lavatories for men and women restrooms.
4. Submit plumbing and electrical plans with riser diagrams.
5. Foundation plan shall be design by an Engineer.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.