Notes:
3258 AC, 4396 SF, SFR / 2 STORY
5/20/2006 12:00:00 AM
01. ***ENERGY STAR***-------------------
disregard this note, this home is not Energy Star----------6-19-07-------JM
02. COMPLIANCE WITH THE APRIL 2006 CONTRACTOR GUIDELINE REQ'D
03. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS
09. BEAMS=10"W X 26"D.
23. GARAGE MUST BE A MIN. 18'W X 20'D CLEAR SHEET ROCK TO SHEET ROCK.
29. TEMPERED GLASS AT FLOAT GLASS WINDOWS GREATER THAN 9 SQ FT, LESS THAN 18" OFF FINISH FLOOR, WITHIN 3'-0" OF A WALKING SURFACE.
46. FRONT ENTRY CURB CUT PER ENCLOSED DESIGN SKETCH.
49. SAME 3RD PARTY RATER MUST DO ALL INSPECTIONS & TESTING OF SUPPLY AND EXHAUST DUCT(S) AND DAMPERS TO MEET ENERGY STAR/GREEN BLDG REQUIREMENTS..
50. CSST GAS PIPING ALLOWED - SEE INFO SKETCH IN LOBBY AND (OR) ORDINANCE(S) 03-07-58 & 03-07-59.
54. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
2nd FLOOR: 3-BED ROOMS,2-BATHS AND GUEST SUITE OVER GARAGE.
BONUS SUITE OVER GARAGE MUST HAVE AT LEAST ONE ESCAPE WINDOW MINIMUM SIZE 3050.