Notes:
4-14-06 jm
1. maintain IBC 1008.1.9. req'mts. for panic hardware and exiting.
2. all wood used in construction shall be fire treated.
3. one hour separation between shop and classrooms, offices, storage (UL # U465) or fire sprinkled.
4. glass at 1 hr. separation wall shall be rated.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
REFER TO APPROVED PLANS FOR NOTES.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
CALL 972-335-5586 TO REQUEST INSPECTIONS.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
2108 SQ FT, SCHA / FRISCO HIGH SCHOOL AG BARN ADDN/ALT