Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- ALL CONSTRUCTIONS TO BE NON-COMBUSTIBLE PARTITIONS WITH 5/8" GYP. BD & METAL FRAMING @ 16" O/C. (PARTITIONS TO CLG MAY HAVE MIN. 2 1/2" STUDS. HIGHER PARTITIONS MIN. 3 5/8" STUDS & GAUGE AS PER SPANNING). ANY WOOD BLOCKING MUST BE FIRE-RES.-TREATED.
3- APPLICANT HAS DECLARED USE OF NITROUS OXIDE (N2O) & OXIGEN (O2) FOR WHICH A 1HR RATED CLOSET TO STORAGE THE GAS CONTAINERS MUST BE PROVIDED AS PER NFPA 99 REGULATIONS HAVING 1 HR RATED DOOR & DIRECT OUTSIDE VENTING AS REQ'D. (A SUGGESTED GAS CLOSET LOCATION HAS BEEN MARKED ON DWG A1, BUT, IN CASE OF INCORRECT DECLARATION, THIS CLOSET MAY BE OMITTED ONLY AFTER RECEIVING A DOCTOR'S LETTER CERTIFYING ABSOLUTE NO USE OF MED GASES IN THE FACILITY).
4- DOCTOR SHALL BE RESPONSIBLE FOR SANITARY FINISH MATERIALS AND FOR CONSULTING A MEDICAL PHYSICIST IF ANY BUILT-IN RADIATION SHIELDING IS NEEDED.
5- SERVER CLOSET & MECH'L/ELECT'L ROOM TO HAVE FULL HEIGHT 1 HR PARTITIONS (TO DECK) WITH 5/8" TYPE 'X' GYP BD OR STOP UNDER 1 HR CLG WITH DOUBLE LAYER OF 5/8" TYPE 'X' GYP BD. THESE ROOMS MUST HAVE 45 MINUTE DOORS (SWINGING OUT) IN 1 HR FRAMES.
6- SUITE'S DOORS LEADING TO EXIT CORRIDOR TO BE 20 MINUTE IN 1 HR FRAME.
7- CORRIDOR WALL MUST BE 1 HR TO DECK. ALL RATED WALLS TO SATISFY THE UL-U465 DESIGN. NO PLBG IS ALLOWED INSIDE A DEMISING RATED WALL. (WHEN PLBG OCCURS, ADDITIONAL FURRED-OUT FINISH MUST BE PROVIDED TO COVER ROUGH PLBG).
8- PROVIDE FIRE/SMOKE COMBINATION DAMPERS AT DUCTS PENETRATING RATED WALLS OR AS REQ'D BY INSPECTORS.
9- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
1850 SQ FT, CIFO / DR. HARA