Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PUBLIC SALES AREA NEEDS TWO MEANS OF EGRESS WITHOUT EXITING THRU THE STOCKROOM AREA (SEC. 1004.2.3). PROVIDE 1 HR RATED EXIT CORRIDOR (WITH 1 HR EXIT DOOR ASSEMLIES) LEADING TO MALL SERVICE CORRIDOR.
3- FRONT ENTRANCE DOORS AND BACK EXIT DOOR MUST BE RECESSED AND SWING OUTWARD AS REQ'D.
4- LONG WINDOW DISPLAY AREA TO BE GATED AT THE SALES AREA END FOR EMPLOYEES ONLY ACCESS.
5- SUBMITTED DWGS MUST HAVE LANDLORD'S STAMP OF APPROVAL AND LANDLORD'S REVIEW COMMENTS AS PER MALL CRITERIA.
5- SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTION.
(9-30-05)
REVISED PROJECT SET, DATED DELTA 2: 9-14-05 AND MARKED WITH LANDLORD'S REVIEW STAMP, HAS BEEN RESUBMITTED AND HEREBY APPROVED WITH THE FOLLOWING ADDITIONAL COMMENTS:
1- EXITING FROM THE LONG DISPLAY WINDOW AREA MUST BE PROVIDED AT BOTH ENDS AS REQ'D. (THE SALES AREA END MAY BE DESIGNED WITH DOOR, GATE, FLUSH PANEL OR OTHER APPROVED CONTROLLABLE SYSTEM TO PREVENT PUBLIC ACCESS INTO THE DISPLAY WINDOW AREA).
2- BACK DOOR TO EXIT CORRIDOR TO BE 1 HR RATED (DOOR & FRAME) WITH 18 INCHES MIN. SPACE AT LATCH SIDE.
2805 SQ FT, CADD / BRIGHTON COLLECTABLES