Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- SUBMIT ENLARGED DETAILS SHOWING DESIGN FOR A VALID 1 HR FIRE/SMOKE CONNECTION OF DEMISING WALLS WITH THE EXACT EXISTING LOCATION OF STOREFRONT'S MULLIONS AS REQ'D. (DEMISING WALLS ENDING AGAINST GLASS ARE NOT PERMITTED).
3- ADD HI/LO DRINKING FOUNTAIN AS REQ'D. (IF BOTTLED WATER WITH CUP DISPENSER IS PROVIDED, IT MAY BE ACCEPTABLE ONLY FOR THE REQ'D LOW PART, BUT MUST BE COMBINED WITH A STANDARD HEIGHT DRINK'G FOUNTAIN TO SATISFY THE HIGH PART).
4- RESUBMIT UPDATED ARCHITECTURAL PLAN (POSSIBLY IN 1/4" SCALE OR WITH 1/4" SCALE AREA PLAN DTLS) SHOWING A DESIGN SOLUTION WITH THE ADDITION OF A SECONDARY RESTROOM FACILITY AS REQ'D FOR OCCUPANCY LOADS EXCEEDING 15 PEOPLE TOTAL.
5- RESUBMITTED DWGS MUST MAKE CLEAR THAT NO PLBG PIPING SHALL BE INSTALLED INSIDE THE DEMISING WALLS.
6- TDLR REGISTR'N NUMBER MUST BE SUBMITTED TO VALIDATE THIS PERMIT IF JOB VALUE IS EXPECTED TO REACH $50,000 OR MORE.
7- PENDING SUBMITTAL OF VALID ASBESTOS SURVEY/STATEMENT FOR THE EXISTING SHELL (SB 509) AND ASBESTOS STATEMENT FOR MATERIALS USED IN THE NEW PART OF CONSTRUCTION (HB 1927).
8- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
1300 SQ FT, CIFO / TIPS & TOES