Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATION AND REVIEW COMMENTS.
2- PROVIDE 1 HR RATED DEMISING WALLS AND ELECT'L CLOSET. (WALLS OF ELECTRICAL CLOSET MAY TERMINATE AT CEILING IF THE CLOSET'S CLG IS ALSO 1 HR RATED).
3- PLBG IS NOT ALLOWED TO BE INSIDE OF RATED DEMISING WALLS (USE SIDE WALLS OR CHASE-OUT WITH ADDITIONAL FURRING AS REQ'D).
4- PROVIDE PROPER GAGE OF MTL STUDS ACCORDING TO SIZE & SPAN. TOP TRACKS OF FULL HT MTL STUDS (TO DECK) MAY NOT BE SECURED TO UNDERSIDE OF DECK WHEN @ ROOF. (STABILIZE WALL BY BRACING IT TO ROOF'S STRUCT'L FRAMING AS REQ'D).
5- DUCTS RATED PENETRATIONS MUST BE TYPICALLY PROVIDED WITH FIRE/SMOKE COMBINATION DAMPERS UNLESS OTHERWISE INSTRUCTED BY BLDG INSPECTORS IN SPECIFIC CASES.
6- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
1803 SQ FT, CIFO / FOOT & ANKLE CENTER OF PLANO