Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE, LOCAL REQUIREMENTS AND REVIEW COMMENTS.
2- WALLS OF RECEPTION ROOM & SERVER ROOM MUST BE FULL HEIGHT 1 HR RATED WALLS TO UNDERSIDE OF DECK AND FIRE SEALED AS REQ'D. ANY GLAZED OPENING IN THESE RATED WALLS MUST BE PROTECTED WITH SPRINKLER HEADS SPACED 3'-0" O/C ON BOTH SIDES.
3- RAISED FLOOR IN SERVER ROOM MUST BE OF NON COMBUSTIBLE CONSTRUCTION AND ACCESSIBLE AS PER NFPA-75 & NEC 1999. PROVIDE 3'-0" MIN. WIDE RAMP WITH MAX. 1 TO 12 SLOPE AND HAND RAILS AS REQ'D.
4- DOOR TO SERVER ROOM TO BE MIN. 45 MINUTE FIRE RATED.
5- SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWERS, FIRE MARSHAL AND FIELD INSPECTIONS.
9400 SQ FT, CALT / SKYWIRE EXPANSION