Notes:
2440 AC, 3229 SQ FT, SFR / 2 STORY
4/26/2003 12:00:00 AM
2. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
9. BEAMS=10"W X 26"D.
26. TEMPERED GLASS REQ'D AT MASTER BATHTUB WINDOW.
54. CSST GAS PIPING PROHIBITED IN FRISCO.
63. RECESSED LIGHT FIXTURES MUST BE 2000 IECC CODE COMPLIANT.
64. STC OF 45 REQ'D BETWEEN UNITS.
67. 12 SEER ALONG WITH R-6 DUCT WORK REQ'D FOR 2000 IECC COMPLIANCE IN NON ENERGY STAR/GREEN BLDG CONSTRUCTION.