Notes:
3061 AC, 3572 SQ FT, SFR / 2 STORY
3/15/2003 12:00:00 AM
2. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
10.BEAMS=10"W X 28"D.
24. EXITWAYS (HALLWAYS) MUST BE A MIN. 36"W INCLUDING ARCHED OR CASED OPENINGS. (TWO OR MORE ROOMS)
25. TEMPERED GLASS REQ'D AT WINDOWS WITHIN 2' OF DOOR OPENINGS.
26. TEMPERED GLASS REQ'D AT MASTER BATHTUB WINDOW.
46. CO DETECTORS REQ'D ON ELECT LEGEND & ELECT PLAN 1/1000 SQ FT & 1 PER FLOOR MIN PLUS (1) ADD'L AT GARAGE ENTRY IN AC AREA.
54. CSST GAS PIPING PROHIBITED IN FRISCO.
63. RECESSED LIGHT FIXTURES MUST BE 2000 IECC CODE COMPLIANT.
64. ATTIC VENTILATION PER IRC R.806.2.
67. 12 SEER ALONG WITH R-6 DUCT WORK REQ'D FOR 2000 IECC COMPLIANCE IN NON ENERGY STAR/GREEN BLDG CONSTRUCTION.
(03/15/2003 13:38 JC)2nd. floor w/ (3) B.R.'s, (2) baths and game room