Notes:
930 SQ FT, CIFO / EDWARD JONES INVESTMENTS
12/2/2002 12:00:00 AM
) Code Compliance: 2000 IBC, IPC, IMC, IECC, 1999 NEC, 1997 UFC
2) Demising walls must be built to UL-U465 design for (1) hr. rating
3) Inter. partitions built to the ceiling must be braced to struct. above.
4) Flex-duct must not exceed 5' in lenght from rigid dist. duct.
5) interior glazing must be tempered glass.
6) (3) exit lights and (2) emergency lights req'd. (1) in the toilet rm.
7) floor drain req'd. in toilet rm.
8) toilet rm. must be ADA in design and equipment.