Notes:
2277 AC, 2936 SQ FT, DPLX / 2 STORY
11/25/2002 12:00:00 AM
2. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
22. EXITWAYS (HALLWAYS) MUST BE A MIN. 36"W INCLUDING ARCHED OR CASED OPENINGS. (TWO OR MORE ROOMS)
30. SECOND FLOOR SIDING AREA MUST NOT EXCEED 50% OF THE TOTAL NET EXPOSED WALL AREA.
43. SEE SOUND TRANSMISSION CODE COMPLIANCE DATA SHEET ATTACHED.
44. CO DETECTORS REQ'D ON ELECT LEGEND & ELECT PLAN 1/1000 SQ FT & 1 PER FLOOR MIN PLUS (1) ADD'L AT GARAGE ENTRY IN AC AREA.
53. CSST GAS PIPING PROHIBITED IN FRISCO.
62. CORRECT FUTURE PLOT PLANS TO MEET 4/2002 CONTRACTORS GUIDELINE REQUIREMENTS.
63. RECESSED LIGHT FIXTURES MUST BE 2000 IECC CODE COMPLIANT.
67. 12 SEER REQ'D FOR 2000 IECC COMPLIANCE IN NON ENERGY STAR/GREEN BLDG CONSTRUCTION.
(11/25/2002 08:26 JC)Beams 10"w x 36" D. Revise plan STC to code reqm't. attached. 2 nd. floor w/ (2) B.R.'s, (2) Baths, and loft above Dining Rm.(07/26/2002 13:35 NJ)
BEAMS=10"W X 30"D.
ADD CARBON-MONOXIDE DETECTOR LOCATIONS TO LEGEND & PLANS.
CORRECT FUTURE PLOT PLANS TO MEET 4/2002 CONTRACTORS GUIDELINE REQUIREMENTS.
CO DETECTORS REQ'D 1/1000 SQ FT & 1 INSIDE AT GARAGE/AC SPACE.
SHOW LOCATIONS OF WATER, GAS VALVES, & AC COMPRESSORS ON PLANS.
2ND FLOOR MUST BE A MIN. 50% MASONRY.