Notes:
1- CONTINGENT UPON COMPLIANCE WITH ALL PERTINENT CODES AND BLDG DEPT REVIEW COMMENTS.
2- SUBDIVIDE FLOOR INTO TWO FIRE AREAS WITH MIN. 1 HR CONTINUOUS FIRE BARRIER AS REQUIRED BECAUSE OF THE PROJECT'S ONLY TWO EXITS (INSTEAD OF THREE EXITS AS PER CODE).
3- RECEPTION AREA ENCLOSED BY 1 HR PARTITION DUE TO THE USE OF FRAMELESS ENTRY GLASS DOORS AS DESIGNED.
4- PROVIDE PROTECTED EXIT PATHWAY (LEADING TO THE STAIRWAY EXIT) WITH SMOKE CURTAINS/SPRINKLER HEADS SYSTEM AS REQUIRED.
5- ANY VARIATIONS OR REVISION MUST BE PRE-APPROVED PRIOR CONSTRUCTION.
6- SUBJECT TO FIRE MARSHAL AND FIELD INSPECTIONS.
35069 SQ FT GE CAPITAL CARD SVCS OFFICE