Notes:
5/9/2018 8:52:46 AM
PERMIT IS FOR ONE 900 SQ FT TENT FOR GROUND BREAKING CEREMONY TO CONTAIN 100 CHAIRS.
PERMIT DOES NOT AUTHORIZE EVENT OR MISC. STRUCTURES.
MAY NOT OBSTRUCT FIRE LANE, HANDICAP PARKING & ACCESSIBILITY, MANDATORY PARKING, STREET TRAFFIC, RIGHT OF WAY, OR VISIBILITY(VAM).
MAY MOUNT ONE BANNER NOT TO EXCEED 48 SQ FT TO TENT WITHOUT ADDITIONAL PERMIT.
ALL AIRBORNE DEVICES (FLAGS, PENNANTS, BALLOONS, ETC.) ARE PROHIBITIED PER ORDINANCE 16-03-25.
SMOKING PROHIBITTED IN ENCLOSED SPACES. REGULATED PER ORDINANCE #06-11-18.
ANY/ALL FOOD PROVISIONS MUST BE APPROVED BY THE HEALTH AND FOOD SAFETY DEPARTMENT UNDER SEPERATE TEMPORARY HEALTH PERMIT.
SUBJECT TO APPROVAL BY FIRE MARSHAL AND POLICE DEPARTMENT.
PERMIT VALID may 9, 2018.
CALL FIRE MARSHAL OFFICE FOR TENT INSPECTION AT LEAST ONE WORKING DAY IN ADVANCE AT 972-292-6328.
JOHN GILLETTE 5/8/2018 7:38:44 PM
TEMP TENT
We have received and reviewed the proposed site location and documentation for one temporary tent structures in accordance with ordinances adopted by the City of Frisco. This is being provided for the grand opening of the new building on the site. The location and use were found acceptable subject to the following comments:
1. An inspection from the Fire Marshal’s Office is required prior to occupancy. Need to call the Fire Marshal’s Office at 972-292-6328, when the tent and equipment are set and ready for inspection.
2. Need to post the occupant load sign for the tent. The occupant load is as follows:
a. 30 feet by 30 feet tent- 128 people
3. Need to provide (2) exits spaced at equal intervals around the perimeter of the tent. Minimum width of each exit is 72 inches wide. Exit openings must comply with the 2015 IFC Chapter 31. Aisle widths must be a minimum of 44 inches. Exits shall be maintained per the 2015 IFC and IBC.
4. Illuminated exit signs shall be provided over each required exit.
5. The means of egress shall be illuminated with light having an intensity of not less than 1 foot candle at the floor level while the structure is occupied. The means of egress illumination fixtures shall be supplied from a separate circuit or source of power.
6. Two sources of power shall be provided.
a. One source of power must be from an approved emergency system.
b. System must be installed in accordance with the ICC Electrical Code.
c. If supplied, the generator will need to be placed a minimum of 20 ft. from tent.
7. Need to provide (1) 2A10BC “ABC” fire extinguisher for the tent. Travel distance to a fire extinguisher cannot exceed 75 feet.
a. The fire extinguisher must have a current inspection tag.
b. The fire extinguisher shall be placed in the path of egress and mounted so that its top is not more than 5 feet above the floor.
8. Need to provide and post a “NO SMOKING” signs on all (4) sides of the interior of each tent structure.
9. Smoking or cooking is not permitted under tent structures.
10. Heating equipment, if installed, will need to comply with the International Fuel Gas Code, the International Mechanical Code, ICC Electrical Code, and approved by the fire code official.
a. Heating equipment shall not be located within (10) feet of exits or combustible material.
b. LP Gas containers less than 500 gallons or less shall have a minimum separation between the container and structures of not less than (10) feet.
11. Must meet all the minimum requirements of the International Fire Code and Building Code.
12. Additional requirements may be required when a site inspection is conducted.
13. Tent needs to be installed within 150 feet of a fire lane to meet the Fi