Notes:
9/16/2019 4:49:35 PM
-OTHER STRUCTURES MUST BE SUBMITTED SEPARATELY.
-ALL FOUNTAINS MUST BE PERMITTED SEPARATELY OUTSIDE POOL ENCLOSURE.
-PRE-PLASTER INSPECTION DURING POOL CONSTRUCTION CANNOT BE APPROVED UNTIL PERMANENT ENCLOSURE IS INSTALLED AND APPROVED.
-POST-CONSTRUCTION ENGINEER LETTER WILL BE REQUIRED AT POOL FINAL.
SALES OFFICE, RESIDENCES AND RECREATION BUILDING DOOR MUST NOT OPEN DIRECTLY INTO A POOL YARD. A WALL OF A BUILDING MAY NOT BE USED AS PART OF A POOL YARD ENCLOSURE UNLESS EACH WINDOW IS PERMANENTLY CLOSED AND UNABLE TO BE OPENED.
-PROJECT MUST COMPLY WITH POOL ORDINANCE, TDSHS MINIMUM STANDARDS FOR POOLS AND SPAS, HEALTH & SAFETY CODE CHAPTER 757 AND PIWF LAW AND ADA RULES. THIS INCLUDES SITE DECK AND POOL LIGHTING, RESTROOMS, ON-DECK SHOWER, EMERGENCY PHONE, POOL ENCLOSURE AND LIFEGUARD REGULATIONS.
-(3C) GATE HARDWARE UNAPPROVED FOR POOL ENCLOSURE; MUST SUBMIT FOR APPROVAL PRIOR TO POOL FINAL.
-GATES OF THE ENCLOSURE MUST BE LOCKABLE; LATCH MUST BE INSTALLED AT MIN. 60 INCHES ABOVE GROUND OR LOWER IF:
1) LATCH INSTALLED ON POOL YARD SIDE OF GATE AND IS AT LEAST 3 INCHES BELOW THE TOP OF THE GATE; AND 2) THE GATE OR ENCLOSURE HAS NO OPENING GREATER THAN ONE-HALF INCH IN ANY DIRECTION WITHIN 18 INCHES OF LATCH INCLUDING THE SPACE BETWEEN GATE AND GATE POST.
OR, 3) A GATE LATCH MAY BE AT 42 INCHES OR HIGHER IF IT CANNOT BE OPENED EXCEPT BY KEY, CARD OR COMBINATION ON BOTH SIDES OF THE GATE.
-COORDINATION WITH POOL CONTRACTOR IS IMPERATIVE.
-NO CLIMABLE HAZARDOUS WITHIN 36 INCHES OF OUTSIDE OF POOL ENCLOSURE. ENSURE THERE ARE NO MASONRY CLIMB HAZARDOUS WITHIN 36 INCHES OF OUTSIDE OF POOL ENCLOSURE.
-LAVATORIES ARE REQUIRED TO HAVE HOT AND COLD WATER TEMPERED AT A MAXIMUM 110 DEGREES VIA THERMOSTATIC MIXING VALVE. RESTROOMS SHALL HAVE BABY CHANGING TABLES.
WOMEN’S SHALL HAVE COVERED TRASH CAN OR FEMININE WASTE RECEPTACLE WITH COVER.
-LIGHTING FOR DECKS AND WATER SURFACES SHALL BE SPACED TO PROVIDE ILLUMINATION TO ALL PORTIONS OF THE DECK AND WATER SURFACE AREAS; BE NOT LESS THAN 0.5 WATTS PER SQ. FT. OF COMBINED WATER/DECK SURFACE AREAS. IF UNDERWATER LIGHTING IS PROVIDED AND IS 0.5 WATT PER SQ. FT WATER SURFACE AREA, THIS AREA NEED NOT BE CALCULATED IN DECK LIGHTING REQUIREMENT.
-DECK GAPS BETWEEN DECK AND WALKWAYS MAXIMUM HORIZONTAL CLEARANCE OF 3/16 INCH.
-DECK VERTICAL ELEVATION BETWEEN DECK AND WALKWAYS MAXIMUM DIFFERENCE OF ¼ INCH.
-MUST PROVIDE ALL GAUGES ON EACH PUMP SYSTEM, INCLUDING PRESSURE OUTLET GAUGE ON FILTER OUTLET PIPING.
-ALL FILTRATION SYSTEM MUST BACKWASH TO SANITARY SEWER SYSTEM INCLUDING RECIRCULATION SYSTEM. ALL FILTRATION SHALL HAVE MEANS TO OBSERVE WASTE DISCHARGE EITHER BY FREE FALL OR SIGHT GLASS.
SKIMMERS – POOL: 4 REQUIRED/4 PROVIDED
RETURNS – POOL: 7 REQUIRED/9 PROVIDED (5 FLOOR RETURNS).
PROVIDE BATHER LOAD 129.
SQ. FT – 2008 SQ FT; 2 SET OF LIFE SAFETY EQUIPMENT
-LIFE SAFETY: 2 SET OF THE FOLLOWING ONE NON-ELECTRICALLY CONDUCTED, NON-TELESCOPING, TWELVE (12) FOOT OR GREATER SIZE POLE WITH ‘SHEPHERD’S CROOK-TYPE HOOK’ & ONE (1) ¼ TO 3/8 INCH DIAMETER THROWING ROPE A LENGTH OF TWO-THIRDS THE MAXIMUM WIDTH OF THE POOL ATTACHED TO A USCG APPROVED RING BUOY OF 15 TO 24 INCH DIAMETER REQUIRED FOR EVERY 2000 SQUARE FEET OR PORTION THEREOF.
-PROVIDE MEANS TO OBSERVE WASTE DISCHARGE EITHER BY FREE FALL OR SIGHT GLASS; SIGHT GLASS MUST BE REMOVABLE FOR CLEANING.
-COPING, HANDHOLDS, ROCKS, STONES, OR OTHER MATERIALS THAT ARE PART OF WATER OR OTHER
FEATURES MAY NOT PROTRUDE MORE THAN 2" PAST THE POOL BEAM.
-ALL SUCTION SUMPS MUST BE INSTALLED PRIOR TO B-STEEL INSPECTION.
EACH SUCTION SYSTEM INCLUDING CIRCULATION, BOOSTERS, WATER FALLS AND FEATURES MUST HAVE AN APPROVED ASME/ANSI A112.19.17 SVRS AND BE INSTALLED BY A CERTIFIED INSTALLER TRAINED AND CERTIFIED BY THE MANUFACTURER OF THE DEVICE.
-ALL AUTO FILL LINES MUST HAVE RPZ.
-SVRS REQUIRED FOR COVERS OR GRATES LESS THAN 24-INCH DIAGONAL IN WATER 4 FT DEEP OR LESS.
-ANTI-VORTEX DRAIN COVERS WITH APPROVED STAMP ARE REQUIRED. THERE SHALL BE NO ENTRAPMENT HAZARDS. SUCTION OUTLETS SHALL BE MINIMUM OF 3FT. APART MAXIMUM 20 FT. AND PLACED AT THE LOWEST POINT OF THE POOL.
-EMERGENCY PHONE SHALL BE LOCATED ON THE OUTSIDE OF THE POOL BARRIER WITHIN 100 FEET UNIMPEDED DISTANCE OF THE POOL AREA AND AVAILABLE 24 HOURS. PHONE LOCATION SIGN REQUIRED INSIDE BARRIER IF PHONE NOT VISIBLE FROM THE CENTER OF THE POOL OR SPA.
o SIGNAGE REQUIRED AT ALL PUBLIC GATES/ENTRIES DESIGNATING LOCATION OF EMERGENCY PHONE.
o CLEAR INSTRUCTIONS FOR PHONE MUST BE PROVIDED BY SIGNAGE.
o ADDRESS MUST BE POSTED AT PHONE.
-TRASH RECEPTACLES: SHALL BE AVAILABLE, COVERED AND RODENT-PROOF. NUMBER SHALL BE DETERMINED BY SIZE OF POOL.
-FILTRATION: THERE SHALL BE MEANS TO OBSERVE WASTE DISCHARGE EITHER BY FREE FALL OR SIGHT GLASS.
-DRINKING FOUNTAIN: AT LEAST ONE SHALL BE PROVIDED.
-CHAIRLIFT/ADA ACCESS: CHAIR MUST BE AVAILABLE TO PATRONS AT ALL TIMES OF POOL OPERATION.
-LIGHTS: GFCI SHALL BE TESTED PRIOR TO POOL FINAL INSPECTION AND EVERY YEAR THEREAFTER. LIGHTS SHALL COMPLY WITH ALL ELECTRICAL REQUIREMENTS. POOL LIGHT GFCI SHALL BE RETESTED WHEN OVERCURRENT PROTECTION HAS BEEN CHANGED, REPAIRED, ALTERED OR AS REQUIRED.
-ENSURE POOL SIGNAGE INCLUDES THE FOLLOWING:
PLEASE NOTE HEIGHT REQUIREMENT OF ALL LETTERS IN EACH SIGN WHERE PROVIDED.
1. “WARNING – NO LIFEGUARD ON DUTY” LETTERS MINIMUM FOUR (4”) INCH HIGH. REQUIRED IF NO LIFEGUARD PROVIDED.
2. “CHILDREN SHOULD NOT USE POOL WITHOUT ADULT SUPERVISION” LETTERS MINIMUM TWO (2”) INCH HIGH. REQUIRED IF NO LIFEGUARD PROVIDED.
3. “NO DIVING” AND THE INTERNATIONAL SYMBOL FOR NO DIVING. LETTERS MINIMUM FOUR (4”) INCH HIGH. REQUIRED IN DECKING OR COPING ALSO.
4. “ADULTS SHOULD NOT SWIM ALONE”.
5. “FOR EMERGENCY DIAL 911” OR APPROPRIATE PHONE OPERATING INSTRUCTIONS. LETTERS MINIMUM ONE (1”) INCH HIGH. FOR EXAMPLE: “PUSH BUTTON TO DIAL 9-1-1”.
6. “NO GLASS IN POOL AREA”.
7. “SWIMMERS MUST SHOWER BEFORE ENTERING SWIMMING POOL/SPA”.
8. “NO ANIMALS IN POOL AREA”.
9. “(PHYSICAL ADDRESS OF POOL)” REQUIRED NEXT TO PHONE AND LEGIBLE.
10. “(LOCATION OF EMERGENCY PHONE AT ALL POOL BARRIER ENTRANCES)”.
11. “FOR EMERGENCY DIAL 911” (4” LETTERS).