Notes:
420 SQ FT, CIFO / ORIGINS
10/13/2014 12:00:00 AM
ontingent upon compliance with review comments, code requirement and pertinent legislations. Reference approved redlines plans and plan review history document for any & all plan review comments.
All work performed must meet the 2012 IBC, IMC, IPC, IFC, IECC, & 2011 NEC Standards, abide by the City of Frisco Zoning Ordinance (11-04-09) and all other city ordinances and local amendments .
All subcontractors must validate and obtain current registration with the city prior to start of project.
Subject to M.E.P. & fire marshal reviews and field inspections. Call (972) 292-5386 for inspection.
***issuance of building permit does not include fire marshal approval. Separate submittal for fire marshal review, fire sprinkler, fire alarm, fire underground, and /or any additional requirements as set forth by the fire department need to be submitted directly to the fire marshal office for approval. Subject to the Federal ADA requirements.
Kiosk shall comply with IBC 2012 section 402.6.2.
1. Millwork to meet TAS requirements. Need ADA access door and 5'-0" ADA turning radius.
2.The exterior of the kiosk must be constructed of a non combustible material such as metal or fire retardant-treated wood (FRT).
3.Aluminum composite material (ACM) having a spread flame index of not more than 25 and a smoke- developed index of not more than 450 per ASTM E-84.
4.The minimum horizontal separation between the kiosk and other structures is 20 feet.
5. Subjectto M.E.P. reviews, fire marshal, field inspections and ADA requirements.
6. Per IBC 2012 chapter 34, Restricts removal or abrogation of fire protection and safety systems and device in existing structure.