Notes:
COMMERCIAL PLAN REVIEW GENERAL NOTES
B10-0905
CITY APPROVED PERMIT SET SHALL REMAIN ON SITE THROUGHOUT CONSTRUCTION/REMODEL, NO EXCEPTIONS.
A. CONTINGENT UPON COMPLIANCE WITH BLDG CODES & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
B. ALL PARTS OF THE BLDG ENVELOPE MUST MATCH OR EXCEED THE MIN. INSULATION REQUIREMENTS OF IECC, WITH R-13 FOR WALLS, R-19 FOR ROOF DECK. DROP-IN CEILING IS NOT PART OF THE ENVELOPE.
C. SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
D. TEMPERED WINDOWS/GLASS WHERE APPLICABLE.
E. FULLY SPRINKLED.
F. INTERIOR FINISHES: GROUP—A2 CLASS--C
FLAME SPREAD ------------76 TO 200
SMOKE DEVELOPED------- 0 TO 450
G. DEMISING WALLS SHALL BE RATED 1 HR. FIRE SMOKE CONSTRUCTION, ALL PENETRATIONS THRU DEMISING WALLS SHALL BE FIRE CAULKED FLOOR TO ROOF DECK.
H. ANY DUCT PENETRATIONS THRU DEMISING WALLS SHALL HAVE FIRE/SMOKE DAMPERS INSTALLED—EXPANDING CAULK PROHIBITED.
A SMOKE DETECTOR IS REQ’D. WITHIN 5’.
I. ALL WOOD BLOCKING SUPPORTING MILLWORK, STANDARDS & EQUIPMENT SHALL BE (FRT) FIRE TREATED WOOD.
(WHERE INSTALLED, ROOF HATCH ACCESS SHALL BE FIRE SMOKE SEALED).
K. MILLWORK TO MEET ADA/TAS REQUIREMENTS.
M. ANY FUTURE RATED WALL ENDING AT THE STOREFRONT MUST PROVIDE 1 HR FIRE/SMOKE CONNECTION TO THE NEAREST MULLION OR PILASTER.
(11/22/2010 1:23 PM MBW)
REVISED BUILDING PLANS APPROVED.
5300 SQ FT, CIFO / EDOHANA HIBACHI & SUSHI dba EDOKO SUSHI