Notes:
5000 SQ FT, CIFO / STAYOUNG FITNESS
11/19/2007 12:00:00 AM
A- CONTINGENT UPON COMPLIANCE WITH P+Z & CIVIL ENGG APPROVALS OF SITE PLAN, BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
B- DUMPSTER ENCLOSURE AREAS TO COMPLY WITH CITY CRITERIA'S STANDARD DETAILS AND ALL SYSTEM TO BE APPROVED BY THE ENVIRONM'L DEPT PRIOR STARTING ANY CONSTRUCTION.
C- ALL PARTS OF THE BLDG ENVELOPE MUST MATCH OR EXCEED THE MIN. INSULATION REQUIREMENTS OF IECC, WITH R-11 FOR WALLS, R-20 FOR ROOF.
D- STOREFRONT GLAZING TO BE 1" INSULATED GLASS TO PROVIDE MAX. SHGC=0.6 AND MAX. U=0.7. (MUST CONFORM WITH SAFETY GLASS REGULATIONS. ALSO ANY FUTURE RATED WALL ENDING AT THE STOREFRONT MUST PROVIDE 1 HR FIRE/SMOKE CONNECTION TO THE NEAREST MULLION OR PILASTER).
E- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
1. Tempered glass/windows where req'd.
2. ADA compliant showers TAS 4.23.8.
3. Fully sprkled. space, II-B construction.
4. Mandatory occupant (100) load sign must be posted, IBC 2003, 1004.3
5. All work subject to fire marshal/city approved inspections and testing.
6. Interior finishes: Group A Class B flame sprd. 26-75, smoke dev. 0-450.
7. UL-U465 1 hr. demising walls floor to roof deck, fire seal floor to roof deck, any pipe/duct penetrations shall have fire/smoke dampers installed.
8. 1 hr. fire/smoke connection to mullion.
9. Vestibule req'd. w/ 3718 sq.ft of open space IECC 2001 802.3.5
10. Office 101 door must be moved to accommodate vestibule.
11. Life safety---single front door must be labeled as emergency exit only, with panic hardware installed--see plans.