Notes:
100 SQ FT, CIFO / MOBILE SOLUTIONS
10/17/2007 12:00:00 AM
COMMERCIAL PLAN REVIEW NOTES
MOBILE SOLUTIONS
STONEBRIAR MALL
1. NOTES ATTACHED TO PERMIT SET FOR KIOSK REQ'MENTS.
2. COUNTER HEIGHT SHALL BE ADA COMPLIANT.
3. INTERIOR FINISHES:
GROUP M CLASS B
FLAME SPREAD 26-75
SMOKE DEVELOPED 0-450
4. ALL WOOD SHALL BE FRT WOOD.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED. (I/O AND LARGER ONLY WITH STABIL-ALLOY SERIES 6000 & 8000)
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.