Notes:
1. ANY WOOD USED FOR BLOCKING, BACKING, SIDING, ETC., MUST BE FIRE RESISTANT TREATED AS REQ'D.
2. ALL OTHER SEPARATIONS FOR EXITWAYS, TENANT DEMISING WALLS, HAZARDOUS STORAGES, ELECTRICAL ROOMS, ETC., TO BE MIN. 1 HR RATED AS REQ'D. (TENANTS AREAS OPENED TO MAIN SALES AREA TO HAVE THE 1 HR BULKHEAD WALL FROM ROOF DECK TO ABOVE THE OPENING, FORMING A MIN. 12" SMOKE VALANCE DOWN FROM THE TENANT AREA'S CLG & PROTECTED BY ONE LINE OF DELUGE TYPE SPRINKLER HEADS @ 4' O/C). PROPOSED ACCORDION-TYPE FIRE & SMOKE DOORS TO BE ACCESSIBLE AUTOMATIC WON-DOOR TYPE, OR APPROVED EQUAL. DUCTS PENETRATING RATED WALLS TO BE PROVIDED WITH FIRE/SMOKE COMBINATION DAMPERS AS REQ'D.
3. ELECT'L DISTRIBUTION CTR UNIT IN SPACE 154 (NEXT TO HALLWAY 161) TO BE 1 HR RATED AS PER APPROVED SHOP DWGS. OTHER EDC EQUIPMENT LOCATED ELSEWHERE TO BE PLACED IN 1 HR RATED ELECT'L ROOMS WHITH RATED DOORS SWINGING OUTWARD AS REQ'D.
4. GYP. BD SHALL NOT BE LESS THAN 5/8" THICK AS TYPICAL CONDITION FOR COMMERCIAL PROJECTS.
5. SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL, HEALTH DEPT., ENVRONM'L DEPT. AND FIELD INSPECTIONS.
200000 SQ FT, CIFO / DILLARDS DEPT STORE