Notes:
7899 SQ FT, CALT / AMERICAN EAGLE OUTFITTERS
1/26/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. PARTITION TYPE C USED TO SEPARATE THE INCIDENTAL AREA (STOCKROOM) FROM MAIN OCCUPANCY (MERCANTILE) SHALL HAVE 5/8 " THICK DRYWALL ON BOTH SIDES FROM FLOOR TO THE UNDERSIDE OF THE DECK TAPES AND SEALED AIRTIGHT TO MEET THE REQUIREMENTS OF A SMOKE PARTITION AND DOORS WITH CLOSING DEVICE SHALL NOT BE UNDERCUT IN EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH NFPA 80 (2003 IBC 302.1.1.1).
2. PARTITION TYPE C USED IN EXIT ACCESS CORRIDOR SHALL BE CONSTRUCTED WITH 1-HOUR FIRE RATED WALL CONSTRUCTION FROM FLOOR TO THE UNDERSIDE OF THE DECK, TAPED AND SEALED AIRTIGHT.
3. FITTING ROOMS 1 & 2 CLUSTERED TOGETHER IS REQUIRED TO HAVE ONE OF IT'S ROOM TO BE ADA COMPLIANT (2003 IBC 1109.12.1).
4. ANY WOODS USED IN A TYPE II-B CONSTRUCTION SHALL BE FIRE RETARDANT WOOD.
5. RESTROMM FLOOR AND WALLS SHALL HAVE A HARD, SMOOTH AND NON-ABSORBENT SURFACE.
6. SAFETY GLAZING AS REQUIRED IN 2003 IBC 2406.
7. ANY MEMBRANE PENETRATIONS SHALL NOT REDUCED THE FIRE RESISTANCE RATING OF THE 1-HOUR FIRE RATED DEMISING WALL AND SMOKE PARTITION WALL.
8. MUST COMPLY WITH LANDLORDS COMMENTS.
9. SUBJECT TO FIELD REVIEW AND INSPECTION.