Notes:
1000 SQ FT, CIFO / SALON 423
8/7/2006 12:00:00 AM
1. Revised plans submitted last 8/4/2006.
2. Submit signed statement of code compliance form.(7/18/2006 10:00 PPB)
Comments and requirements;
1. The bottle water stated in the letter from Jackie Nguyen shall be permitted only if its FREE and if its a bottled water dispensers only 50% of the required number of the drinking fountain is permitted and the HI portion drinking fountain is still required.
2. Submit the furniture or equipment/chair layout.
3. Egress from corridor 105 shall not pass through backroom/storage 106 as per IBC 1013.2 Submit revision.
4. Electrical fixtures penetrating the 1-hour demising wall shall not reduced the fire resistance required.
5. Cutting the slab due to plumbing works shall not reduce the structural integrity of the structure, Submit letter from Professional Engineer.
6. 1-hour fire resisitve demising wall is required between tenant spaces.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.