Notes:
1553 SQ FT, CIFO / SHI
7/14/2006 12:00:00 AM
1. The codes that City of Frisco adopted was all in 2003 edition except for 2002 NEC therefore design should be based on 2003 edition of ICC codes.
2. In 2003 IBC Table 302.1.1 storage/stock room over 100 sqft. shall be separated by 1-hour fire resistive barrier construction or provide sprinkler system. The mall has installed fully sprinkler system therefore the code only requires that the incidental use area shall be separated by construction capable of resisting the passage of smoke (smoke partition), the partitions shall extend from the floor to the underside of the roof deck above, door shall be self closing or automatic and shall not have air transfer openings as per IBC 302.1.1.1. Resubmit floor plan and wall detail showing this requirements by the code before permit will be issue.
3. Smoke dampers required on duct openings that penetrates the smoke partition wall as per IBC 710.7. Submit revised mechanical plan showing smoke damper.
(7/13/2006 14:10 PPB)
1. response letter was submitted.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.