Notes:
54574 SQ FT, CNEW / MAIN STREET AND WORLD CUP WAY
7/27/2006 12:00:00 AM
Plan review comments:
1. Structural members and assemblies that supports the 1-hour fire rated corridor shall have a 1-hour fire protection rating.
2. 5/8" thk. type "X" gypsum board shall be used on all exterior walls that enclosed a structural column and girders that support the beam.
3. Flour tropper shall not reduced the fire resistance rating of the 1-hour fire rated ceiling assemblies, therefore it should be fire rated.
4. Subject to field inspection.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.